Q: Na yɛwɔ 90% voltage na yɛtee "Snap" (flashover) a ɛyɛ nnam wɔ tank no mu. Nhyehyɛe no hwee ase. So ɛsɛ sɛ yebue GIS no na yesiesie mprempren?
A: Ɛnyɛ nea ɛkyerɛ ankasa. Wɔfrɛ eyi sɛ Self-Clearing Flashover.
"Mmiɛnsa-Strike" Mmara (IEEE/IEC):
1. Strike 1: Sɛ flashover ba a, yi system no fi mu na san fi sɔhwɛ no ase.
2. Hwɛ: Sɛ flashover a ɛtɔ so mmienu no ba wɔ Higher Voltage sene deɛ ɛdi kan no a, ɛkyerɛ sɛ anyinam ahoɔden no "hyee" burr ketewa bi a ano yɛ nnam anaasɛ abɔdeɛ bi. GIS no reyɛ nea ɛho tew kɛse.
3. Strike 2/3: Sɛ flashover no si wɔ Same anaa Lower Voltage a, wowɔ ɔhaw ankasa (insulator a apaapae anaasɛ structural defect kɛse bi). GYAE sɔhwɛ no ntɛm ara.
Atemmu: Flashover biako a ɛno akyi no, wɔde simma 1 kura mu yiye wɔ voltage a edi mũ mu no taa yɛ nea wogye tom sɛnea IEC 62271-203 kyerɛ no.
Yɛbɛyɛ dɛn apaw sɔhwɛ ahoɔden ama "on-site" sɔhwɛ?
Q: Me GIS no yɛ 220 kV. So ɛsɛ sɛ mesɔ hwɛ wɔ ahoɔden koro no ara a adwumayɛbea no de dii dwuma wɔ wɔn Type Test no mu no so?
A: DABI. Field test voltages no sua sɛnea ɛbɛyɛ a wɔbɛkwati "Over-stressing" mfiri a wɔde amena dedaw na wɔadi ho dwuma.
"80% Mmara" no:
1. Factory Test: Wɔsɔ GIS no hwɛ wɔ deɛ ɔyɛeɛ no mu wɔ 100% wɔ standard withstand level (sɛ nhwɛsoɔ no, 460 kV ma 220 kV nhyehyɛeɛ).
2. Field Test: Yɛtaa de 80% di dwuma wɔ adwumayɛbea sɔhwɛ ahoɔden (sɛ nhwɛso no, 368 kV).
3. Bere tenten: Mpɛn pii no simma 1 wɔ 80% level no so.
Dɛn nti na 80%? Ɛyɛ kari pɛ. Ɛkorɔn araa ma wubehu mfomso biara a ɛwɔ nhyiam mu anaasɛ akwantu mu ɔsɛe, nanso ɛba fam araa ma sɛ sintɔ ketewaa bi wɔ hɔ a, ɛremma insulators no nyin daa.